Chapter 2 Specification of Communication port for CPU module
2 – 21
[Sample program of EHV-CPU3]
R0
WRF601 = H0001
Opens the ASR port 1 at the rising edge o
f
R0.
DIF
WRF600.0
WRF601 = H0000
DFN
The ASR port open request flag falls whe
n
the ASR port 1 is closed.
R1
Performs the event transmitting at the
rising edge of R1.
S
WRF601.1 DIF
WRF600.1
The event transmitting completion flag,
the event transmitting request flag, and R1
fall when the event transmitting is
completed.
R
WRF601.1 DIF
WRF600.1
R1
R
R
[Sample 3]
Network consists of EHV-CPU and Web controller as follows, and the Control Editor sets the ASR communication of
EHV-CPU. ASR communication of Web controller is set using the Web browser. The setting information of
EHV-CPU4 and Web controller is as follows.
The connection is established between EHV-CPU4 and Web controller in two seconds later after RUN of EHV-CPU4,
16-word data from WR0 to WRF of EHV-CPU4 is transmitted from EHV-CPU to Web controller at one second
interval. In Web controller, the received data is stored in WR0 to WRF. And 16-word data from WR10 to WR1F of
Web controller is transmitted from Web controller to EHV-CPU4, and the received data is stored in WR10 to WR1F
in EHV-CPU4.
Web c o ntroller
(Passive, Send / Receive)
EHV-CPU4
(Active, Send / Receive)
Data sending and receiving
Figure 2.22 Connection diagram of Sample 3